XK-W2001 (SMY-W2001) is a temperature controller, a relay for external control in a housing with a wire into a socket.
Key Features:
Supply voltage: AC 220V
Consumption: 50mA/80mA relay enabled
Maximum switching current 7 A 220V (1500W)
Temperature range: -50 ~ 110°C
Measurement accuracy: ±0.2s
Temperature accuracy: ±0.1s
Measuring input: NTC 10kOhm, L = 1m waterproof sensor
Saves settings after power supply voltage drops
Programming thermo temperature controller XK-W2001
To set the XK-W2001 for heating:
Enter the menu by pressing the SET button
In P0 mode, press SET and use the arrows to set the temperature for turning on the thermostat, for example 50 degrees. And press the SET button to save the data.
Use the arrows to select mode P1, press SET and use the arrows to set the temperature for turning on the thermostat, for example 90 degrees. And press the SET button to save the data.
Wait 10 seconds for the thermostat to return to operating mode. In this mode, the device will turn on at a temperature of 50 degrees and turn off when it reaches 90 degrees.
To configure the XK-W2001 device for cooling:
Enter the menu by pressing the SET button
In P0 mode, press SET and use the arrows to set the thermostat switch-on temperature, for example 90 degrees. And press the SET button to save the data.
Use the arrows to select mode P1, press SET and use the arrows to set the temperature for turning on the thermostat, for example 90 degrees. And press the SET button to save the data.
Wait 10 seconds for the thermostat to return to operating mode. In this mode, the device will turn on at a temperature of 90 degrees and turn off when the temperature drops to 50 degrees.
Menu items:
P0 - setting the switching temperature.
P1 – setting the shutdown temperature.
P2 - temperature calibration.
P3 - pause before turning on the load. When the readings reach the specified level, the time relay is turned on. Example: the temperature reached 90 degrees, and after 5 minutes it drops again to 89 degrees, as a result we get frequent switching on and off, which is not always acceptable. Here you will need a time relay, i.e. switch-on delay when the set temperature is reached. Default is 0.
Leave your feedback or ask a question
Only this product is discussed here. Off topic comments will be deleted! Please follow the Commenting Rules.
The data presented in the product description are for reference only and may differ from those indicated by the manufacturer.
To carry out technical calculations and obtain the exact parameters of the goods, use the datasheets from the manufacturer's website.
If you need additional information, or you found an error in the description, or have other questions about this product, then our manager will help you: Денис - Днепр
unknown